Buy Now STANDARD EQUIPMENT
30kW
- 3.0L Liquid Cooled 40kW
- 3.9L Liquid Cooled 50kW
- 3.0L Liquid Cooled 55kW
- 5.4L Liquid Cooled 70kW
- 3.9L Liquid Cooled 70kW
- 6.8L Liquid Cooled 80kW
- 5.4L Liquid Cooled 100kW
- 5.4L Liquid Cooled 100kW
- 6.8L Liquid Cooled 130kW
- 6.8L Liquid Cooled 150kW
- 6.8L Liquid Cooled 11 kW
15, 20 & 25 kW 30
kW & 40 kW
| Transfer Switches
| Generator Control Panel
Quiet-Test Mode For
Low Noise Exercise -60 dB(A) at 23 feet Generac 3.0L Engine
Naturally Aspirated Gaseous Fueled
GENERATOR SPECIFICATIONS TYPE ..........................................................................................................Synchronous ROTOR INSULATION ..........................................................................................Class H STATOR INSULATION ........................................................................................Class H TOTAL HARMONIC DISTORTION ........................................................................<3.5% TELEPHONE INTERFERENCE FACTOR (TIF) ........................................................<50 ALTERNATOR OUTPUT LEADS 3 PHASE............................................................4 wire BEARINGS ....................................................................................................Sealed Ball COUPLING ..................................................................................................Flexible Disc LOAD CAPACITY (STANDBY RATING) ................................................................30 kW EXCITATION SYSTEM............................................................................................Direct NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards. GENERATOR FEATURES Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Insulation is Class H rated at 150 °C rise All models are fully prototyped tested VOLTAGE REGULATOR TYPE ................................................................................................................Electronic SENSING ....................................................................................................Single Phase REGULATION ..........................................................................................................± 1% FEATURES................................................................................................V/F Adjustable Adjustable Voltage and Gain LED Indicators CONTROL PANEL FEATURES SIX LED INDICATOR LIGHTS: Overcrank shutdown Overspeed shutdown Low coolant level shutdown High coolant temperature shutdown Low oil pressure shutdown Low battery voltage System ready for operation No utility sensing Exerciser not set (in auto mode only) Low fuel pressure Delay on utility failure for engine start Engine warmup before transfer Delay to retransfer to utility Delay to retransfer to utility Engine cooldown timer INTERNAL FUNCTIONS: 3 position switch (auto, off and manual) 2 wire start for any transfer switch Communicates with the Generac RTS transfer switch Built-in 7 day exerciser Selectable engine speed at exercise Governor controller is built into the master control board Temperature range -40 °C to 70 °C |
ENGINE SPECIFICATIONS MAKE ................................................................................................................ Generac MODEL..................................................................................................................V Type CYLINDERS ..................................................................................................................6 DISPLACEMENT ................................................................................................3.0 Liter BORE ........................................................................................................................3.55 STROKE......................................................................................................................3.1 COMPRESSION RATIO ..........................................................................................9.3:1 INTAKE AIR SYSTEM........................................................................Naturally Aspirated VALVE SEATS ..................................................................................................Hardened LIFTER TYPE ....................................................................................................Hydraulic GOVERNOR SPECIFICATIONS TYPE ................................................................................................................Electronic FREQUENCY REGULATION ..................................................................................± 1% STEADY STATE REGULATION ............................................................................± 1/2% ADJUSTMENTS Speed......................................................................................................Yes Droop ......................................................................................................Yes ENGINE LUBRICATION SYSTEM OIL PUMP ................................................................................................................Gear OIL FILTER ..........................................................................................Full flow cartridge CRANKCASE CAPACITY ..................................................................................4 Quarts ENGINE COOLING SYSTEM TYPE ....................................................................................................................Closed WATER PUMP ................................................................................................Belt driven FAN SPEED..............................................................................................................1800 FAN DIAMETER................................................................................................18 inches FAN MODE............................................................................................................Pusher FUEL SYSTEM FUEL TYPE ..........................................................................Natural gas, propane vapor CARBURETOR ..............................................................................................Down Draft SECONDARY FUEL REGULATOR ..................................................................Standard FUEL SHUT OFF SOLENOID ..........................................................................Standard OPERATING FUEL PRESSURE..................................................................5” - 14” H2O ELECTRICAL SYSTEM BATTERY CHARGE ALTERNATOR ............................................................12V 30 Amp STATIC BATTERY CHARGER ..............................................................................2 Amp RECOMMENDED BATTERY ......................................................................24F 625CCA SYSTEM VOLTAGE ............................................................................................12 Volts |
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
COMMERCIAL 30 kW | |||
KW RATING | 30 | ||
ENGINE SIZE | 3.0 Liter V-6 | ||
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 120/240V, 1-phase, 1.0 pf 120/208V, 3-phase, 3.0 pf 277/480V, 3-phase, 3.0 pf | KW 30 30 30 | AMP 125 104 45 | CB Size 150 125 50 |
GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% Single phase or 208 3-phase 480V 3-phase | 60 70 | ||
ENGINE FUEL CONSUMPTION (Natural Gas) Exercise cycle ft3/hr. 25% of rated load ft3/hr. 50% of rated load ft3/hr. 75% of rated load ft3/hr. 100% of rated load ft3/hr. | 70 111 214 298 412 | ||
ENGINE COOLING Air flow (inlet air including alternator and combustion air) ft3/min. Coolant capacity US gal. Heat rejection to coolant BTU/hr. Max. operating air temp. on radiator ˚C (˚F) Max. ambient temperature ˚C (˚F) | 2460 2.5 115,000 60 (150) 50 (140) | ||
COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz cfm | 92 | ||
SOUND EMISSIONS IN DBA Exercising at 7 meters Full load at 7 meters | 60 73 | ||
EXHAUST Exhaust flow at rated output 60 Hz cfm Exhaust temp. at muffler outlet ˚F | 240 925 | ||
ENGINE PARAMETERS Rated synchronous RPM 60 Hz HP at rated KW 60 Hz | 1800 48 | ||
POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3% for every 10 ˚C above - ˚C 1.65% for every 10 ˚F above - ˚F Altitude Deration 1% for every 100 m above - m 3% for every 1000 ft. above - ft. | 25 77 183 600 |
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. KW rating is based on LPG Fuel and may derate with natural gas.
All specifications are subject to change without notice.
30 kW Commercial Generator Liquid Cooled Generac Generator - Single phase or Three phaseSitemap | Website Design by Search Engine First Place