Generators Online
Quiet-Test Mode For
Low Noise Exercise 62 dB(A) at
23 feet Generac
5.4L Engine Naturally Aspirated Gaseous Fueled
STANDARD EQUIPMENT
| FEATURES
|
• | Innovative design and fully prototype tested | • | Built-in kW, kVAR and power factor meters |
• | UL2200 Listed | • | Watertight electrical connectors |
• | Solid state frequency compensated digital | • | Rodent proof construction |
voltage regulator | • | High efficiency, low distortion Generac designed alternator | |
• | Dynamic and static battery charger | • | Vibration isolated from mounting base |
• | Sound attenuated acoustically designed enclosure | • | Matching Generac transfer switches engineered and |
• | Quiet test for low noise level exercise | tested to work as a system | |
• | Acoustically designed engine cooling system | • | All components easily accessible for maintenance |
• | High flow low noise factory engineered exhaust system | • | Electrostatically applied powder paint |
• | State of the art digital control system | • | H-100 microprocessor control panel |
TYPE ..........................................................................................................Synchronous
ROTOR INSULATION ..........................................................................................Class
H NOTE: Emergency loading in compliance with NFPA 99, NFPA 110, paragraph 5-13.2.6. Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards. VOLTAGE REGULATOR TYPE ..............................................................................................................Full Digital SENSING ............................................................................................................3
Phase REGULATION ......................................................................................................±
1/4%
|
GENERATOR FEATURES
Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 ˚C above a 40 ˚C ambient Insulation is Class H rated at 150 ˚C rise All prototype models have passed three phase short circuit testing
CONTROL PANEL FEATURES
TWO FOUR LINE LCD DISPLAYS READ: Voltage (all phases) Current (all phases) Power factor kW kVAR Transfer switch status Engine speed Low fuel pressure Run hours Service reminders Fault history Oil pressure Coolant temperature Time and date Low oil pressure shutdown High coolant temperature shutdown Overvoltage Overspeed Low coolant level Low coolant level Not in auto position (flashing light)
INTERNAL FUNCTIONS: I2T function for alternator protection from line to neutral and line to line short circuits Emergency stop Programmable auto crank function 2 wire start for any transfer switch Communicates with the Generac HTS transfer switch Built-in 7 day exerciser Adjustable engine speed at exerciser RS232 port for GenLink® control RS485 port remote communication Canbus addressable Governor controller and voltage regulator are built into the master control board Temperature range -40 ˚C to 70 ˚C
ENGINE SPECIFICATIONS
MAKE ................................................................................................................ Generac
MODEL ..................................................................................................................V Type
CYLINDERS ..................................................................................................................8
DISPLACEMENT ................................................................................................5.4 Liter
BORE........................................................................................................................3.55
STROKE....................................................................................................................4.17
COMPRESSION RATIO ..............................................................................................9:1
INTAKE AIR SYSTEM........................................................................Naturally Aspirated
VALVE SEATS ..................................................................................................Hardened
LIFTER TYPE ....................................................................................................Hydraulic
GOVERNOR SPECIFICATIONS
TYPE ................................................................................................................Electronic
FREQUENCY REGULATION ..................................................................................± 1%
STEADY STATE REGULATION ............................................................................± 1/2%ADJUSTMENTS Speed......................................................................................................Yes
Droop ......................................................................................................Yes
ENGINE LUBRICATION SYSTEM
OIL PUMP ................................................................................................................Gear
OIL FILTER ..........................................................................................Full flow cartridge
CRANKCASE CAPACITY ..................................................................................5 Quarts
ENGINE COOLING SYSTEM
TYPE ....................................................................................................................Closed
WATER PUMP ................................................................................................Belt driven
FAN SPEED..............................................................................................................1800
FAN DIAMETER................................................................................................26 inches
FAN MODE..............................................................................................................Puller
FUEL SYSTEM
FUEL TYPE....................................................................................................Natural gas
CARBURETOR ..............................................................................................Down Draft
SECONDARY FUEL REGULATOR ..................................................................Standard
FUEL SHUT OFF SOLENOID ..........................................................................Standard
OPERATING FUEL PRESSURE..................................................................5”
- 14” H2O
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR ............................................................12V 30 Amp
STATIC BATTERY CHARGER........................................................................12V 2 Amp
RECOMMENDED BATTERY ......................................................................24F 625CCA
SYSTEM VOLTAGE ............................................................................................12 Volts
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
OPERATING DATA
KW RATING ENGINE SIZE GENERATOR OUTPUT VOLTAGE/KW - 60Hz 120/240V, 1-phase, 1.0 pf 120/208V, 3-phase, 3.0 pf 277/480V, 3-phase, 3.0 pf GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% Single phase or 208 3-phase 480V 3-phase ENGINE FUEL CONSUMPTION (Natural Gas) Exercise cycle ft3/hr. 25% of rated load ft3/hr. 50% of rated load ft3/hr. 75% of rated load ft3/hr. 100% of rated load ft3/hr. ENGINE COOLING Air flow (inlet air including alternator and combustion air) ft3/min. Coolant capacity US gal. Heat rejection to coolant BTU/hr. Max. operating air temp. on radiator ˚C (˚F) Max. ambient temperature ˚C (˚F) COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz cfm SOUND EMISSIONS IN DBA Exercising at 7 meters Full load at 7 meters EXHAUST Exhaust flow at rated output 60 Hz cfm Exhaust temp. at muffler outlet ˚F ENGINE PARAMETERS Rated synchronous RPM 60 Hz HP at rated KW 60 Hz POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3% for every 10 ˚C above - ˚C 1.65% for every 10 ˚F above - ˚F Altitude Deration 1% for every 100 m above - m 3% for every 1000 ft. above - ft. | KW 100 100 100 | COMMERCIAL 100 kW 100 5.4 Liter V-8 AMP CB Size 417 500 347 400 150 200 190 225 232 371 713 994 1374 5900 4.0 380,000 60 (150) 50 (140) 325 62 75 975 925 3600 155 25 77 182 600 |
---|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. KW rating is based on LPG Fuel and may derate with natural gas.
100 kW
NON-TERMINATED
GENERAC® POWER SYSTEMS, INC. P .O. BOX 297 WHITEWATER, WI 53190WEBSITE: www.guardiangenerators.com
03.05 2005 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.