- Quiet, powerful Generac OHVI single-cylinder
or V-Twin engines fueled by natural gas or LP gas.
- UL
Listed remote-mounted pre-wired automatic transfer switch with 8, 10 or 12 circuit
emergency load center for fast and efficient unattended transfer to generator
when utility power fails.
- A standard weather
protective enclosure with sound-absorbing panels protects generator from harmful
weather and also reduces exterior noise levels. Includes key locks for security.
- Hinged top and removable front panel for easy
serviceability.
- Built-in charger maintains
battery at optimum performance level.
- Automatic
safety shutdowns protect engine and generator in event of low oil pressure, high
temperature, overspeed and/or overcrank.
- Automatic
seven-day exerciser runs the system for twelve minutes weekly to maintain top
running condition.
- Installation system
includes the pre-wired automatic transfer switch with built-in load center, 30'
and 2' wiring harnesses, pre-wired external connection box, 1' flexible fuel line,
"Do-It-Yourself" installation guide and a composite mounting pad.
| |
|
|
Model
Number | 04389 |
Rated
Power LP (kW)Save $$
Portable Generators |
Standby Generators | Air
Compressors |
UPS Uninterruptible Power Sources | Automotive
Parts | 7 |
Rated
Power NG (kW)* | 6 |
Voltage
@ 60 Hz | 120/240 |
Phase | Single |
Frequency | 60
Hz | Amps
LP | 58.3/29.2 |
Amps
NG | 50.0/25.0 |
Engine/Alternator
RPM | 3600/3600 |
Engine | 410
cc. 14.5 HP Generac OHVI Single Cylinder | EPA/CARB
Certified | Yes |
Fuel | Natural
Gas/ LP Vapor | Engine
Cooling | Air |
UL2200 | Yes |
CUL
Listed | Yes |
Main
Line Circuit Breaker | 40
Amp | Dimensions
(L" x W" x H") | 48
x 24 x 28-1/4 | Unit
Wt. (lbs.) | 452 |
|
|
|
Start/Stop
Control | Cyclic
cranking: 7 seconds on, 7 seconds rest. 90 seconds overcrank protection. |
Automatic
Low Oil Shutdown | Standard |
Overspeed
Shutdown | Standard,
72 Hz | Overcrank
Protection | Standard |
Automatic
Voltage Regulator with Over-Voltage Protection | Standard |
Engine
Warmup | 10
seconds | Engine
Cool-Down | 1
minute | Safety
Fuse | Standard |
Starter
Lockout | Starter
cannot re-engage until 5 seconds after the engine has stopped |
2
Amp Timed Trickle Battery Charger | Standard |
Auto
Switch | Utility
failure/7 day exercise | Off
Switch | Stops
unit. Power is removed. Control and charger still operate |
Manual
/ test | Start
with starter control, unit stays on. If utility fails,transfer to load takes place |
|
|
|
| |
|
|
No.
of Poles | 2 |
Current
Rating (amps) | 100 |
Voltage
Rating (VAC) | 250 |
Utility
Voltage Monitor (fixed) Pick-up Drop out |
80% 60% | Return
to Utility | Approx.
13 seconds | Exercises
7 minutes weekly | Standard |
UL
Listed | Standard |
Dimensions
(H" x W" x D") | 26.5
x 12.5 x 7 | |
|
|
Go
to 7, 12 & 15 kW specifications PDF | |